The view menu is not protected by a password, as no changes can be made from within this menu
option. After five minutes it will return to the monitor mode.
Pressing {CHANGE} wil move down through the menu.
At the end of each sub-menu, select {ESCAPE} to return to the higher menu.
13
{INPUT} [SELECT] Enter the input menu
{SENSOR} [SELECT] Enter the sensor menu
{SER NO} [SELECT] Show the sensor serial number, in decimal
{HILIMIT} [SELECT] Show the sensor URL in engineering units
{LOLIMIT} [SELECT] Show the sensor LRL in engineering units
{MINSPAN} [SELECT] Show the sensor’s minimum available span, If
this is exceeded when using turndowns greater
than 20 to 1 an error will be reported.
{RANGEHI} [SELECT] Show, in engineering units, the transmitter URV
corresponding to 20 mA
{RANGELO} [SELECT] Show, in engineering units, the sensor LRV
corresponding to 4 mA.
{DAMPING} [SELECT] Show the damping value in seconds. This is
applied to the analogue and digital output
signals.
{BURNOUT} [SELECT] This shows which direction the analogue output
will go in event of a fatal sensor failure.